Ex cable gland selector
Barrier or compression gland? Answer a few questions and get the answer from BS EN 60079-14:2014, step by step.
Sizes that fit your cable
| Gland | Size and thread | Order code | Seal range |
|---|
Guidance from BS EN 60079-14:2014 clause 10. The equipment certificate, the gland maker's instructions and a competent person decide. Sizes come from the makers' datasheets: check the cable's actual diameters.
Choosing Ex cable glands
When do I need a barrier gland on an Ex d enclosure?
Under BS EN 60079-14:2014 clause 10.4.2, a barrier (compound-filled) gland is needed where the flameproof enclosure contains an internal source of ignition and the gas is group IIC, or it is in Zone 1 with a volume over 2 litres. A barrier gland is also needed if the cable is not substantially compact and filled.
What counts as an internal source of ignition?
Parts that can produce arcs, sparks or high temperatures in normal operation, such as switches, contactors, relays, circuit breakers, fuses and lamps. An enclosure with terminals and connections only does not have one.
Can I use an Ex d gland on an Ex e enclosure?
Yes, if it is also certified for Ex e (most Ex d glands are dual-certified) and keeps the enclosure's IP rating, at least IP54.